FrancaisEnglishDeutsch
 Aquasant AGLevelTurbidityWater treatmentContents / VolumeEngineering 
You are here: Level » Control Systems

Control Systems

Control system Type AS9-E24 (two wire technology)

Technical data
*Ex-classification: [EEx ia] IIC
Auxiliary voltage: 24V AC/DC ±10%
Relay contacts: max. 0.5A, max. 48VAC, max. 50VA
Sensor circuitry: (intrinsically safe, self monitoring)
Uo:7.2V, lo:<68mA, Co:<14,5µF, Lo:<6Mh
Temperature range: -20°C to 40°C
Response delay: 1 sec. ±50%
Type of protection: IP20
Dimensions: European standard board 100 x 160mm
Output: 2 potential-free change-over contacts

Options:
Type VE9 local electronic

To be operated with sensor type: AF24, AF26, AF31, AF32, AF36

*With local electronic type VE9 to be used in [EEx ia] IIC environment together with sensor types: AF1S, AF21, AF23, AF33, AF35, AF42.

The control system AS9-24 offers high disturbance immunity for long (up to 1500m) cable installations.

Controls:
Test button for the functional inspection of the appropriate sensor and the control system.

Self monitoring:
The patented self-monitoring triggers an alarm in case of malfunction of the sensor, a failure in the connection cable, or a fault in the control system.

PDF AS9-E24 Datasheet

Control system Type AS1

Technical data
Ex-classification: [EEx ia] IIC
Auxiliary voltage:230V ±10%, 50Hz
Relay contacts:max. 1A, max. 250VAC, max. 250VA
Sensor circuitry:(intrinsically safe, self monitoring)

Uo :7.2V, lo:77mA, Co:14,5µF, Lo:6mH

Temperature range:-20°C to 40°C
Response delay:1 sec. ±50%
Type of protection: IP54
Dimensions: HxWxD: 132x71x137mm
Output: 2 potential-free change-over contacts

Options: Type AS1.2 with acoustic alarm

To be operated with sensor types: AF1S, AF21, AF23, AF33, AF42

Controls:
Test button for the functional inspection of the appropriate sensor and the control system. Reset key for the acknowledgement of the acoustic alarm. Relay output remains on alarm.

Self monitoring:
The patented self-monitoring triggers an alarm in case of malfunction of the sensor, failure in the connection cable, or fault in the control system.

PDF AS1 Datasheet

Control system Type AS6

Technical data
Auxiliary voltage:
Type AS6.1/AS6.2: 230V ±10%, 50Hz
Type AS6.3/AS6.4: 24VAC/DC ±10%
Relay contacts:max. 1A, max. 250VAC, max. 100VA
Opto electronic coupler: 5..24VDC, 10mA +10%
Sensor circuitry: (intrinsically safe, self monitoring)
Uo :7.2V, lo:82mA
Temperature range: -20°C to 40°C
Response delay: 1 sec. ±50%
Type AS6.2/6.4: 0.5 to 10 sec. -10 ...+50%
Type of protection:IP54
Dimensions: HxWxD: 77x39x92 mm

To be operated with sensor type: AF6

Controls:
Test button for the functional inspection of the appropriate sensor and the control system. Type AS6.2 and AS6.4 cover the option to adjust the sensitivity as well as the response delay of the sensor.

Self monitoring:
The patented self-monitoring triggers an alarm in case of malfunction of the sensor, a failure in the connection cable, or a fault in the control system.

PDF AS6 Datasheet

Control system Type AN3

Technical data
*Ex-classification: [EEx ia] IIC
Auxiliary voltage: 230V ±10%, 50Hz
Relay contacts: max. 1A, max. 250VAC, max. 250VA
Sensor circuitry:(intrinsically safe, self monitoring)
Uo:7.2V, lo:89mA, Co:13,5µF, Lo:5mH
Temperature range:-20°C to 40°C
Response delay: 1 sec. ±50%
Type of protection: IP54
Dimensions: HxWxD: 132x71x137 mm
Output: 2 potential-free change-over contacts (with hold fuction)

To be operated with sensor type: AF24, AF26, AF31, AF32, AF36

*For operation in [EEx ia] IIC T4 environment: Operate with sensor type: AF1S, AF21, AF23, AF33, AF35, AF42.

Controls:
Test button for the functional inspection of the appropriate sensor and the control system.

Self monitoring:
The patented self-monitoring triggers an alarm in case of malfunction of the sensor, a failure in the connection cable, or a fault in the control system.

PDF AN3 Datasheet

Control system Type AS8

Technical data
Ex-classification: [EEx ia] IIC
Auxiliary voltage: 230V ±10%, 50Hz
Relay contacts: max. 1A, max. 250VAC, max. 250VA
Sensor circuitry: (intrinsically safe, self monitoring)
Uo:7.2V, lo:89mA, Co:13,5µF, Lo:5mH
Temperature range: -20°C to 40°C
Response delay: 1 sec. ±50%
Type of protection: IP54
Dimensions: HxWxD: 132x71x137 mm
Output: 2 resp. 3 potential-free change-over contact

Options:
Type AS8.2: With two sensor circuits and two potential free change-over contacts.
Type AS8.3: With three sensor circuits and three potential free change-over contacts.

To be operated with sensor type: AF1S, AF21, AF23, AF33, AF42

Controls:
Test button for the functional inspection of the appropriate sensor and the control system.

Self monitoring:
The patented self-monitoring triggers an alarm in case of malfunction of the sensor, a failure in the connection cable, or a fault in the control system.

PDF AS8 Datasheet

Control system Type AS9 (two wire technology)

Technical data
*Ex-classification: [EEx ia] IIC
Auxiliary voltage: 230V ±10%, 50Hz
Relay contacts: max. 1A, max. 250VAC, max. 250VA
Sensor circuitry: (intrinsically safe, self monitoring)
Uo:7.2V, lo:133mA, Co:13,5µF, Lo:1.3mH
Temperature range:-20°C to 40°C
Response delay:1 sec. ±50%
Type of protection: IP54
Dimensions: HxWxD: 132x71x137 mm
Output: 1,2 or 3 potential-free change-over contacts

Options:
Type AS9.1: with one potential free change-over contact.
Type AS9.2: with two potential free change-over contacts.
Type AS9.3: with three potential free change-over contacts.

Type VE9: Local electronic

To be operated with sensor type: AF24, AF26, AF31, AF32, AF36

*With local electronic type VE9 to be used in [EEx ia] IIC T4 environment together with sensor types: AF1S, AF21, AF23, AF33, AF35, AF42.

The control system AS9 offers high disturbance immunity for long (up to 1500m) cable installations.

Controls:
Test button for the functional inspection of the appropriate sensor and the control system.

Self monitoring:
The patented self-monitoring triggers an alarm in case of malfunction of the sensor, a failure in the connection cable, or a fault in the control system.

PDF AS9 Datasheet

Control system Type AS51-E24 / AS83-E24

Technical data
*Ex-classification:[EEx ia] IIC
Auxiliary voltage: 24V AC/DC ±10%
Relay contacts: max. 0.5A, max. 48VAC, max. 50VA
Sensor circuitry:(intrinsically safe self monitoring)

Uo:7.2V, lo:<68mA, Co:<14,5µF, Lo:<6mH

Temperature range: -20°C to 40°C
Response delay:Type AS51-E24: 1 sec. ±50%

Type AS83-E24: 0.5 to 20 sec. ±50%

Type of protection: IP20
Dimensions: European standard board 100 x 160mm
Output: 2 potential-free change-over contacts

Options:
Type VE9:Local electronic

To be operated with sensor type: AF23, AF26, AF31, AF32, AF36

*For the use in [EEx ia] IIC environment together with sensor types: AF1S, AF21, AF23, AF33, AF35, AF42.

Controls:
Test button for the functional inspection of the appropriate sensor and the control system.
Type AS83-E24 covers the option to adjust the sensitivity as well as the response delay of the sensor.

Self monitoring:
The patented self-monitoring triggers an alarm in case of malfunction of the sensor, a failure in the connection cable, or a fault in the control system.

PDF AS51-E24 Datasheet

PDF AS83-E24 Datasheet